Hello,
Sometimes, my cpu 1515f-2pn goes to “STOP” and I have this message in th log “Data corruption prior to sending to F-IO” The project is developped in Tia portal V16.
Event ID : 16#0D:75D6
Thanks for help!
Please briefly explain why you feel this question should be reported.
Please briefly explain why you feel this answer should be reported.
Please briefly explain why you feel this user should be reported.
Hi,
The safety program put your cpu to STOP.
The data used to calculate your outputs in the safety program changed between start and end of your safety program (OB123).
Please check this siemens guide:
https://support.industry.siemens.com/cs/document/22099875/simatic-industrial-software-s7-distributed-safety-configuring-and-programming?dti=0&lc=en-WW
In your error log I can see that the issue is with your %Q430.0 output.
Please check the network where your %Q430.0 output is writen. maybe the data (inputs and other data) used to calculate this output are changed in other tasks.
Best regards
Hi,
When this happen? is it after you power the machine.
I have the same problem,can you tell me is your problem fixed?
thank you
Hi
It happened sometimes when an acknowledgment occurs after closing a door.
Hi,
I followed your advice and found the network which causes the problem.
The time configured an FDBACK was too short. I increased it and it solved my problem
Have a nice day