Hi Everyone! I use a s7-1500 controller. I use MB_CLIENT function to read data from an other PLC. Everything work fine until I make change in my project and download to the PLC. I have error 80A3 and impossible to acknowledge until I make a stop/Run of the plc. Anyone can help me? Best Regards,
Hi, use P_TRIG to monitior everything in the left of this instruction. It turns to ON for one scan when the entire set of logic to the left goes from off to on use -|P| to monitor a single tag. it turns on one scan when the tag goes from off to on. Best regards
Hi,
use P_TRIG to monitior everything in the left of this instruction. It turns to ON for one scan when the entire set of logic to the left goes from off to on
use -|P| to monitor a single tag. it turns on one scan when the tag goes from off to on.
Best regards
See less
Hi Maesa, If you use instances declared in a FB function. Try to use a global instance of MB_clien like this: use a global DB to declare the "ModbusDataconnectParamClient" structure. This will fix your problem and when you download the project, it will not cause problem for MB_client function. hopeRead more
Hi Maesa,
If you use instances declared in a FB function.
Try to use a global instance of MB_clien like this:
use a global DB to declare the “ModbusDataconnectParamClient” structure.
This will fix your problem and when you download the project, it will not cause problem for MB_client function.
hope this will help you
See less